Follow on Google News | ATSHOCK-P30: protection against overvoltagesATSHOCK-P30: protection against overvoltages caused by direct lightning strike, now in pluggable modules
Type 1 protectors should be able to withstand direct lightning impacts to the line. Therefore, they are tested with 10/350μs current waves, which involve a much higher energy than 8/20μs waves. ATSHOCK-P30 has been checked with 30kA impulsional current, passing all tests described in the standards. The whole protector is designed to withstand that high energy: not only the internal components but also its wiring, formed by a double terminal for assuring a strong connection. Its pluggable format facilitates maintenance and, if necessary, replacement. The let-through voltage of this protector is higher than 1,5kV, so in case of lines supplying electronic equipment it has to be co-ordinated with ATSUB or ATCOVER type protectors, which let appropriate residual voltages for avoiding damages to sensitive devices. + Info about ATSHOCK-P30 (http://lightningprotection- We design and manufacture lightning rods, surge protection devices, storm detectors, earthing systems and exothermic welding. End